Markets Commercial Flashcool Evaporative System
 

Flashcool Evaporative System

 

Report Fields

Project Number ET11SMUD1015
Start Year 2011
End Year 2011
Markets Segments Commercial
Project Type Demand Savings • Electric Energy Savings
Type of Technology HVAC, Commercial
Organization Sacramento Municipal Utility District (SMUD)
Project Status Completed
Savings Type Industry

Nexant, in coordination with HMG, monitored the two AC units with FlashCool for a 14-week period (July 26th to August 12th and August 23nd to November 2nd), and without FlashCool for a two week period (August 12th to August 22nd), to determine the overall impact of the FlashCool Technology on energy consumption, peak demand, and water usage. The analysis findings are:

- Reduced average energy consumption of the AC units by 36,193 kWh a year (AC#1 (LENNOX) by 22,061 kWh/yr and AC#2 (TRANE) by 14,132). The percentage reduction of average energy consumption is 36.9% (AC#1 (LENNOX) by 44.1% and AC#2 (TRANE) by 29.4%).
- Reduced the peak demand of the facility during 4 PM to 7 PM on the hottest days  by 8.3 kW (AC#1 (LENNOX) by 5.0 kW and AC#2 (TRANE) by 3.8 kW). The percentage peak demand reduction is 13.1% (AC#1 (LENNOX) by 16.7% and AC#2 (TRANE) by 11.2%).
- Reduced energy usage of the AC units during summer days from 4 PM to 7 PM by 1,376 kWh a year (AC#1 (LENNOX) by 379 kWh  and AC#2 (TRANE) by 997 kWh ). The percentage reduction of energy usage during peak hours is 19.2% (AC#1 (LENNOX) by 17.6% and AC#2 (TRANE) by 19.7%).
- Maximum water usage rate was 18 gallons per hour for the two AC units.
- The annual water usage is calculated to be 34,559 gallons for the AC units.

Download project report